CONTROLS INSTALLATION

HVAC Controls Installation & DDC Systems

From the panel out — controllers, sensors, actuators, conduit, terminations, programming, and point-by-point commissioning. Done by techs who understand both the controls and the mechanical equipment underneath.

DDC installationField wiringSequence programmingPoint-to-point checkoutMulti-vendor

Direct Digital Control (DDC) is the foundation of every modern commercial HVAC system. The hardware — DDC controllers, sensors, actuators, VFDs, relays, and the panels that house them — is only part of the story. What separates a controls install that performs from one that limps along is whether the contractor understands the mechanical equipment underneath, the sequence of operations that's supposed to govern it, and the discipline of point-by-point commissioning before turnover. Vertex is a controls-first contractor. We install the hardware, write and load the logic, and verify every point against the spec before we hand a building over.

WHAT WE DELIVER

Panel buildout and field wiring

DDC control panels built to spec — enclosures, terminal strips, transformers, surge protection, network switches, and labeled wireways. Field wiring run in EMT and flex conduit, terminated to professional standards, and labeled at both ends.

AHU, VAV, RTU, and packaged equipment controls

Full controls install on air handlers (CHW/HHW coils, economizers, mixed-air dampers, return fans), VAV terminal units (reheat, parallel/series fan-powered), rooftop units, and packaged equipment. Discharge air, mixed air, return air, OA, CO2, occupancy, and equipment status sensing.

Chiller plant and hydronic controls

Chiller staging, condenser water and chilled water reset, primary/secondary pumping, cooling tower fan staging, bypass valve control, and plant-level optimization on top.

Sensor and actuator installation

Temperature, humidity, CO2, occupancy, pressure (static and differential), flow, current, and runtime sensing. Pneumatic, electronic, and electric actuators on dampers and valves, with full stroke verification.

Sequence of operations programming

Written sequences (your engineer's or ours, per ASHRAE Guideline 36 where applicable) implemented in the controller's programming environment. Logic blocks reusable, documented, and version-controlled.

Point-by-point commissioning

Every analog input verified against a calibration reference, every digital input toggled, every analog output stroked, every digital output cycled, and every sequence functionally tested before turnover.

HOW WE WORK

Five stages we run on every controls installation project — adjustable to your timeline, but never skipped.

01

Submittals and engineering

Control system drawings, sequence of operations review, points list, panel schedules, riser diagrams, and product submittals approved before we order materials.

02

Panel fabrication

Panels built to spec — either off-site in a controlled environment or on-site as project requirements dictate. Photo-documented and tested before installation.

03

Field installation

Conduit, wiring, sensor and actuator mounting, panel installation, and network terminations. Daily field reports and clean as-built red-lines.

04

Programming and graphics

Controllers loaded with logic, graphics built (if scope), supervisor binding, and trend / alarm configuration.

05

Point-to-point checkout and commissioning

Pre-functional checklists, point-to-point checkout against the points list, functional performance tests against the sequence, and turnover with documentation.

STANDARDS WE WORK TO

  • ASHRAE Guideline 36-2021
    High-performance sequences of operation for HVAC systems. Our default reference for AHU, VAV, hydronic, and zone control sequences.
  • ASHRAE Standard 135 (BACnet)
    The open protocol our controllers communicate on.
  • NFPA 70 (NEC)
    Field wiring is performed per the National Electrical Code, with local AHJ inspection where required.
  • ASHRAE Standard 62.1
    Ventilation sequences (CO2-based demand controlled ventilation, minimum OA reset) are designed against current ventilation requirements.

TYPICAL PROJECTS

New construction controls scope

GC awards the controls package. We engineer the submittal, build the panels, install the field devices, program the sequences, and commission with the CxA. Turn the building over with documented as-builts and a trained operator.

Controls retrofit

Building with 15-year-old proprietary DDC controllers, no remote access, no usable graphics. We replace controllers with modern BACnet hardware, run new wiring where needed, gateway anything we can't replace yet, and stand up a Niagara supervisor on top.

Tenant fit-out controls

Tenant remodel — new VAV layouts, new zoning, new sequences. We install the new VAV controllers, retie sensors and thermostats, and integrate cleanly with the base-building BAS.

Single-piece-of-equipment install

New rooftop unit, AHU, or chiller installed by a mechanical contractor. We provide and install the controls, integrate it with the existing BAS, and commission the new equipment into the building's sequences.

RELEVANT CASE STUDIES

FAQ

Common questions

Do you work with controllers we already specified, or do you have preferred lines?
Both. We're vendor-flexible — we install and program controllers from Tridium (JACE), Honeywell, Johnson Controls, Trane, Carrier, Distech, Lynxspring, iSMA, and Strato Automation. If you've already specified a line, we work with it. If you haven't, we'll recommend based on the project.
Can you handle the electrical work too, or do we need a separate electrician?
Low-voltage controls wiring is our work. Line-voltage power to controllers, panels, and motorized equipment is typically the electrical contractor's scope, though we coordinate closely and handle disconnects and small motor circuits where appropriate.
Who's on the controls install crew?
A lead controls technician plus support technicians, with a project manager coordinating schedule and submittals. Our techs are cross-trained on mechanical equipment, not just wire-pullers — so issues at the controls/mechanical boundary get diagnosed correctly on the first visit.
What does point-to-point commissioning actually mean?
Every controller point — every input, every output, every internal calculation — is individually verified. Inputs against a known reference (thermometer, manometer, light meter). Outputs by stroke, cycle, and observed equipment response. Documented in a checklist before functional testing begins.
RELATED SERVICES
PLATFORMS WE INSTALL

Have a project to scope?

Free estimate on any controls installation scope — installation, integration, retrofit, or service. We'll write you a clear scope and an honest price.